Standard Specification for Thermoplastic Polyethylene Insulation for Electrical Wire and Cable
Translate name
STANDARD published on 1.10.2020
Designation standards: ASTM D1351-20
Publication date standards: 1.10.2020
SKU: NS-1008086
The number of pages: 4
Approximate weight : 12 g (0.03 lbs)
Country: American technical standard
Category: Technical standards ASTM
This specification covers thermoplastic polymer insulation consisting substantially of polyethylene considered suitable for use on electrical wire or cable with specified maximum conductor sizes that will be used for continuous operation at specified conductor temperatures and maximum voltage ratings for power application or series lighting. Since the insulation material cannot be tested unless it has been formed around a conductor, tests shall then be done on insulated wire or cable in this specification are solely to determine the relevant property of the insulation material and not to test the insulated conductor or completed cable. Materials shall conform to physical properties as to unaged tensile strength and elongation at rupture, tensile strength and elongation at rupture after air oven aging, absorption coefficient, and insulation thickness. Insulations shall also be tested for their electrical performance in terms of AC and DC voltage, partial discharge, and insulation resistance.
Keywords:
cable, conductor, electrical, insulation, polyethylene, thermoplastic, wire ,, ICS Number Code 29.035.20 (Plastic and rubber insulating materials)
1. Scope | ||||||||||||
1.1 This specification covers a thermoplastic insulation which consists substantially of polyethylene. 1.2 This type of insulation is considered suitable for use on wire or cable that will be used for continuous operation at conductor temperatures up to 75 °C with a maximum conductor size of 1000 kcmil (507 mm2). The maximum voltage rating shall not exceed 35 000 V for power application or 9 000 V for series lighting. 1.3 In many instances the insulation material cannot be tested unless it has been formed around a conductor. Therefore, tests done on insulated wire or cable in this specification are solely to determine the relevant property of the insulation material and not to test the insulated conductor or completed cable. 1.4 Whenever two sets of values are stated, in different units, the values in the first set are regarded as standard, while the values in parentheses are provided for information only and are not considered standard. 1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee. |
||||||||||||
2. Referenced Documents | ||||||||||||
|
Do you want to make sure you use only the valid technical standards?
We can offer you a solution which will provide you a monthly overview concerning the updating of standards which you use.
Would you like to know more? Look at this page.
Latest update: 2024-05-12 (Number of items: 2 898 481)
© Copyright 2024 NORMSERVIS s.r.o.