Standard Test Methods for Flash Point of Liquids by Small Scale Closed-Cup Apparatus
Translate name
STANDARD published on 1.6.2020
Designation standards: ASTM D3278-20
Note: WITHDRAWN
Publication date standards: 1.6.2020
SKU: NS-995298
The number of pages: 8
Approximate weight : 24 g (0.05 lbs)
Country: American technical standard
Category: Technical standards ASTM
Keywords:
flash/no flash, flash point, organic peroxides, organic solvents, small scale closed-cup apparatus,
| Significance and Use | ||||||||||||
|
5.1 Flash point is one of the properties used to define the flammability of a liquid. It is used to classify liquids according to their flammability by governmental regulatory agencies. It may also be used to determine the presence of impurities or contaminants in a given liquid, such as the presence of residual solvents in solvent-refined drying oils. See Test Methods D56 and D93 for alternate flash point testing. |
||||||||||||
| 1. Scope | ||||||||||||
|
1.1 These test methods cover procedures for determining whether a material does or does not flash at a specified temperature or for determining the lowest finite temperature at which a material does flash when using a small scale closed-cup apparatus.Note 1: Tests at higher or lower temperatures are possible. Note 2: More viscous materials may be tested in accordance
with Annex A4.
Note 3: Organic peroxides may be tested in accordance with
Annex A5, which describes the
applicable safety precautions.
Note 4: The U.S. Department of Labor (OSHA, Hazard
Communications), the U.S. Department of Transportation (RSPA), and
the U.S. Environmental Protection Agency (EPA) have specified Test
Methods D3278 as one of
several acceptable methods for the determination of flash point of
liquids in their regulations.
Note 5: These test methods are similar to International
Standards ISO 3679 and ISO 3680.
1.2 The values stated in SI units are to be regarded as the standard. The values given in parentheses are for information only. 1.3 This standard should be used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions and should not be used to describe or appraise the fire-hazard or fire-risk of materials, products, or assemblies under actual fire conditions. However, results of the test may be used as elements of a fire-hazard or a fire-risk assessment which takes into account all of the factors which are pertinent to an assessment of the fire hazard or fire risk of a particular end use. 1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. 1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee. |
||||||||||||
| 2. Referenced Documents | ||||||||||||
|
Do you want to make sure you use only the valid technical standards?
We can offer you a solution which will provide you a monthly overview concerning the updating of standards which you use.
Would you like to know more? Look at this page.
Latest update: 2026-08-14 (Number of items: 2 293 479)
© Copyright 2026 NORMSERVIS s.r.o.